  • Description
Product Detail

    Off Load Tap-Changer 
    The main characteristics of this new series of tap changers are: Speed of installation; Safe and exact switch movement; Exact contact positioning after the switching maneuver; Compact dimensions; Possibility to adapt to the thickness of the transformer tank.

    These units may be used with mineral oil or silicon liquid. They are fixed below the transformer cover by a support.
    They allow adjustment or combinations according to the diagrams given in the following pages. There is no need for washers during assembly because the tap changer adjusts itself according to the thickness of the transformer tank.
    Oil tightness is provided by O-rings. The catalogue illustrates normally used tap changers and standard accessories. Special tap changers may be designed to meet special requirements. Tap changing procedures are very quick and simple.
    They must be performed with de-energized transformer in a no-load state. To switch, just lift the knob, rotating it until the desired number or mark coincides with the colored arrow on the washer. Release then the knob and make sure that it is fasten.

    Model Explanation
     WST ? - ?/?-???
        W:  off-circuit
        S :  three-phase or D for single phase
        T :  linear type tap chager
        ?:  voltage regulation model
        ?:  rated current
        ?:  rated voltage
        ?:  number of tapping heads
        ?:  number of tapping position
    Voltage Regulation Model
        I  :  terminal point
        II :   central point
        III :  neutral point
       IV :  Y-? conversion
       V :  series-parallel connection

    Samples Technical Data

    Specifications

    WST 30

    WST 63

    WST 125

    WST 250

    WST 400

    WST 500

    Phase number

    three-phases

    Connection mode

    Central point(?) Neutral Point(?) Terminal Point(?)

    Rated through current(A)

    30

    63

    125

    250

    400

    500

    Short-circuit capacity

    Heat stableness current(KA/2s)

    0.7

    1.6

    2.5

    3.75

    4

    5

    Dynamic stableness current(KA)

    1.8

    4

    6.25

    9.375

    10

    12.5

               Rated frequency

    50~60

    Insulation level(KV)

    Rated Voltage

    10KV

    20KV

    35KV

    Power-frequency withstand Voltage(50Hz/1min)

    42KV

    55KV

    95KV

    Impulse(1.2/50µs)

    75KV

    125KV

    250KV

    Sealing Performance(KPa/24h)

    60

    Machine life(Thousands of times)

    2